Solid Fuel Fired Packaged Boilers

Solid Fuel Fired Packaged Boilers

Product Details:

X

Product Description

Solid Fuel Fired Packaged Boilers

Capacity: From 100 Kg/hr to 10,000 Kgs/hr
Working Pressure: Upto 21 Kg/cm2g
Design Options: Special execution on request

Construction
INDCON manufacture all-welded design, Packaged Boilers in accordance with Indian Boiler Regulations (IBR) and other International Codes like BS-2790 & ISO-R 831 .Boilers quality plates are used and strict quality control checks are enforced for stage-wise inspection of all boilers during manufacturing. All welding seams are 100% radiographed to ensure best quality. These shell type Boilers are in horizontal construction having 3-pass arrangement to ensure good fuel efficiency.

First pass is through the Furnace which is welded to the front tube plate of the boiler and to the reversing combustion chamber which is firmly supported on the rear tube plate by stay bars. Large furnace volume is provided for complete combustion and heat absorption. There are two passes of smoke tubes constituting the second and third pass of the boiler. The man-hole and carefully placed hand-holes are provided for easy inspection and maintenance. Hinged doors are provided at front and rear ends of the boiler to give easy access for inspection, cleaning and replacement of tubes

Standard Scope of Work

  • Boiler with furnace, in dry back or wet back construction, are fitted with front and rear smoke boxes and are mounted on saddles for ease of site installation.
  • Boiler quality tubes are provided in the boiler. Size of tubes, their quantity and pitch are engineered to achieve maximum heat transfer and ensure easy cleaning and maintenance.
  • Sufficient water and steam space are provided to ensure that dry and saturated steam is available and that the Boiler can meet the fluctuation in steam consumption pattern.
    • Solid fuel based Boilers are supplied with Induced Draught (I.D) Fan with a by-pass arrangement complete with ducting and dampers.
    • Oil or Gas Fired Boilers are supplied with Forced Draught (F.D.) Fan to ensure proper combustion of fuel.
  • All boilers are supplied with two Multistage Centrifugal Feed Water Pumps so that one pump is stand-by. duly inspected and approved by chief inspectors of Boilers as per IBR quality.
    Two water level indicators are provided along with an automatic water level controller.
  • Ladder and platform are provided for all sizes of Boilers.
  • Insulation of boiler and refractory lining of smoke boxes are done.
  • Site installation and commissioning of boiler.
  • Training of operating staff at end-user's factory.